Wireless Receivers, Repeaters and Tools | FLTA-KP10 Wireless Receiver for HRP/LPR
FLTA-KP10 Wireless Receiver for HRP/LPR


ASSOCIATED PRODUCTS

DOCUMENTATION
Datasheet (742kB)

FLTA-KP10 wireless receiver has been designed to work with SyxthSense HRP/LRP controllers and TEFL/TEU-FL/KLU-FL wireless sensor range. The FLTA-KP10 has 8 analogue outputs of which six operate as KP10 temperature sensor and two as analogue 0..10Vdc signal. The analogue signals can be used to transmit wirelessly humidity, setpoint, pressure, flow rate, CO2 and digital signals to the controllers.

The wireless range uses 868.30 MHz FSK Modulation and has been designed for reliable operation in wide range of environments. Wireless temperature sensors transmit measurement readings on change, or at least every hour.

FLTA-KP10 module acts also as a Modbus Communication interface for the sensor readings. Using FLTA-KP10 Modbus communication up to 99 sensors can be read over Modbus master such as WebBiter web-browser interface, of which up to 8 sensors can be connected to HRP/LRP via analogue outputs. The FLTA-KP10 control module monitors the room units for any malfunctions and for the low battery level.

Up to 63 FLTA-KP10 control modules (networks) can operate in the same wireless area. Total maximum of 6,237 sensors/transmitters can be connected to the system in a single system.

 
 


Power Supply: 24Vac/dc
RF Transmission: 868.30 MHz FSK Modulation
Transmission Range: Line of sight: Up to 500m
In buildings up to 20..100m depending on wall strcutures
Range can be extended up to 8 times with FLREP repeaters
FLTA Module Outputs: 6 x KP10 Outputs
2 x 0..10Vdc Outputs
Error Signal Output (if Modbus is disabled)

A1: KP10 Output, range: -20..+100°C, resolution 0.37°C
A2: KP10 Output, range: 0..+50°C, resolution 0.32°C
A3: KP10 Output, range: 0..+50°C, resolution 0.32°C
A4: KP10 Output, range: 0..+50°C, resolution 0.32°C
A5: KP10 Output, range: 0..+50°C, resolution 0.32°C
A6: KP10 Output, range: -20..+100°C, resolution 0.37°C
A7: 0..10Vdc Output
A8: 0..10Vdc Output

KP10 outputs can be used for temperature readings from TEFL, KLU-FL and TEU-FL sensors. 0..10Vdc outputs A7 and A8 can be used for setpoints, humidity signals and any other suitable analogue measurement (see signal output options for TEFL, TEU-FL and KLU-FL transmitters).

FLTA Communication:
Modbus RTU (RS485)
Addressing and Configuration: Via Built-In LCD and Buttons
Measurement Options: With TEFL Transmitters
Temperature 0...50°C = KP10, conenct to FLTA Outputs A1 to A6
Humidity 0...100% = 0...10V, connect to FLTA Outputs A7 and A8
Setpoint 18...24C = 0...10V, connect to FLTA Outputs A7 and A8
5-Position Switch 1...5V (e.g.. position 3 = 3V), connect to FLTA Outputs A7 and A8
Digital Input: 0V (Open), 5V (Closed), connect to FLTA Outputs A7 and A8

With TEU-FL Transmitters
Temperature -50...+150°C = KP10, connect to FLTA Outputs A1 and A6
Analogue Input: 0..10Vdc = 0..10Vdc (wireless signal transmission e.g. for HDH CO2 transmitters), connect to FLTA Outputs A7 and A8

With KLU-FL Transmitters
Temperature -50...+150°C = KP10, connect to FLTA Outputs A1 and A6
Humidity 0...100% = 0...10V, connect to FLTA Outputs A7 and A8

Operating Temperature: 0°C...+50°C
Dimensions: 53W x 90H x 58D mm

 £ 168.00 197.40 inc VAT
 